Category: Industrial System Power Line Filters
Introduction: Mechanical DimensioDC filters are mainly used to suppress electromagnetic interference transmitted along DC power lines; they have excellent common mode and differential mode insertion loss over a wide frequency band (150kHz-30MHz); high performance a…
DC filters are mainly used to suppress electromagnetic interference transmitted along DC power lines; they have excellent common mode and differential mode insertion loss over a wide frequency band (150kHz-30MHz); high performance and low temperature rise. Can help all kinds of electronic equipment using DC power supply through TCO99, FCC, VDE and CISPR and other related industry EMC standards.
Widely used in all kinds of DC equipment, such as: automotive electronics test DC source, DC bus power supply, photovoltaic inverter DC side, plating power supply and so on.
Type
|
Rated Voltage
|
Rated Curren
|
Test Current
|
Circuit Diagram
|
Terminal
|
Dim. diagram
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
line-to-line | line-to-ground | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-20F1 | 250V DC | 20A | 500V DC | 1.5kV DC | C.D.2 | M4 | D02 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-30F1 | 250V DC | 30A | 500V DC | 1.5kV DC | C.D.2 | M4 | T02 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-40F3 | 250V DC | 40A | 500V DC | 1.5kV DC | C.D.2 | M6 | D04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-50F3 | 800V DC | 50A | 1.5kV DC | 1.5kV DC | C.D.2 | M6 | D04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-50F6-PV | 1.2kV DC | 50A | 3.0kV DC | 3.6kV DC | C.D.6 |
|
16mm2 | P01 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-150F6-PV | 1.2kV DC | 150A | 3.0kV DC | 3.6kV DC | C.D.6 | 95mm2 | P02 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-200F6-PV | 1.2kV DC | 200A | 3.0kV DC | 3.6kV DC | C.D.6 | 95mm2 | P03 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-250F6-PV | 1.2kV DC | 250A | 3.0kV DC | 3.6kV DC | C.D.6 | 6×25-M10 | P04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-300F6-PV | 1.2kV DC | 300A | 3.0kV DC | 3.6kV DC | C.D.6 | 6×25-M10 | P04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-400F6-PV | 1.2kV DC | 400A | 3.0kV DC | 3.6kV DC | C.D.6 | 6×25-M10 | P04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-500F6-PV | 1.2kV DC | 500A | 3.0kV DC | 3.6kV DC | C.D.6 | 8×25-M10 | P04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-600F6-PV | 1.2kV DC | 600A | 3.0kV DC | 3.6kV DC | C.D.6 | 8×25-M10 | P04 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-800F6-PV | 1.2kV DC | 800A | 3.0kV DC | 3.6kV DC | C.D.6 | 8×40-M14 | P05 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-1000F6-PV |
1.2kV DC |
1000A |
3.0kV DC |
3.6kV DC |
C.D.6 |
8×40-M14 |
P05 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
SF-1200F6-PV | 1.2kV DC | 1200A | 3.0kV DC | 3.6kV DC | C.D.6 | 10×50-M14 | P06 |
❈❈ F series conventional rated voltage 250V, 600V, 800V, 1200V other voltage requirements please contact customized.
Contour | Drawing number | L | W | H | T | P | J | K | S | E | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
P04 | F17 | 300 | 140 | 110 | 240 | 165 | 190 | 416 | M10 | M10 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
P05 | F17 | 300 | 150 | 140 | 240 | 175 | 200 | 430 | M14 | M12 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
P06 | F17 | 300 | 160 | 150 | 240 | 185 | 210 | 430 | M14 | M12 |
Previous: D/T/TH Series
Next: M Series
1.Main useMainly used to enter the shielded room signal line transmission, such as telephone lines, fax lines, security m…
(1) Determine the performance index of the filter based on the design requirements;(2) Approaching the performance index …
Often factories use sine wave filters for daily filtering work, while the excellent foil winding structure and aluminum l…